Data Center Electrical Calculator
Data Center Cooling Load Calculator (Tons of Refrigeration)
Preliminary IT-load-driven cooling capacity sizing in tons of refrigeration, with an other-heat-gains allowance and a redundancy margin.
Design Inputs
Results
Total Heat Load
110.00 kW
Cooling Capacity Needed
31.28 TR
Installed Capacity incl. Redundancy
39.10 TR
IT heat load (1 TR = 3.517 kW) dominates a data hall's cooling load; "Other Heat Gains" is a lumped placeholder for lighting, people and envelope/solar gains, which need a proper room-by-room heat-load study for a real design — treat this as a preliminary IT-load-driven estimate only, not a substitute for one.
Explore more calculators
Conductor Sizing
Free HV (HT) and LV cable sizing calculator, plus busduct and earth cable size calculation. Four IEC/IS-aligned tools in one place, each checking ampacity, voltage drop and short-circuit withstand rather than giving a rough estimate.
Transformer Sizing
Size a power transformer to the nearest standard IEC 60076 kVA rating from connected load, power factor and spare capacity, with primary and secondary full-load current.
UPS Selection
Size a UPS system across Single, N, N+1, Distributed, 2N and 2(N+1) redundancy philosophies, with losses, battery charging load, and standard kVA rating libraries.
Generator (DG) Sizing
Size a standby diesel generator set per ISO 8528, sized on the larger of steady-state running load and the voltage-dip-limited starting requirement of the largest motor.